product-img
Product images are symbolic photos
product-img
Product images are symbolic photos
For industrial- and wiring purposes. Usable in the open, in dry, damp and wet environments in the open and concealed,
as well as in masonry and in beton, not suitable for imbedding in solidified or compressed concrete.
Outdoor usage is only possible, as long as the cable is protected against direct sunlight.

The materials used are free from silicon and cadmium and free from varnish damaging sustances.

Nominal voltage Uo/U: 300/500 kV
Test voltage 2000 V
Bending radius fixed (xD) 4
Operating temperature fixed -40°C bis 70°C
Operating temperature mobile 5°C bis 70°C
Fire classes Eca
Standard YM: ÖVE / ÖNORM E 8242
NYM: DIN VDE 0250-204:2000-12,
self-extinguishing and flame-retardant
to VDE 0482-332-1-2, DIN EN
60332-1-2, IEC 60332-1
Standard CE CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.
inner Conductor solid bare copper conductor to DIN VDE 0295
cl. 1, BS 6360 cl. 1 and IEC 60228 cl. 1
core Insultation Polyvinyl chloride (PVC)
Core colour code acc. HD 308 S2
layer ores stranded in layers with optimal laylength
inner Sheath Material Filler
Outer sheath material Polyvinyl chloride (PVC) TM1, to DIN
VDE 0281 part 1
(N)YM-J
Art.Nr

Net amount
Metal surcharge
Total amount